If it is processing of carbon ceramic in the semiconductor industry, environmental measures, power factor improvement, the efficiency improvement of working process, new heater development, leave it to Sanko Co., LTD.

Product line-up

VieZA

 VieZA product specification
Form
S-APR300200-1
Control scheme
Alternating-current-voltage peak value control
dimension /1 zone
W:240mm×H:900mm×D:450mm
Weight/1 zone
75kg
Cooling system
Air cooling with blower
Operating ambient air temperature
-10℃ - 50℃ (without dew condensation)
Input power source One zone
For heaters
Single phase AC200V±10% 50/60Hz 250Arms TB1-1, 2 terminal
For synchronous power supplies
Single phase AC200V±10% 50/60Hz 0.1Arms CN1-1, 2, 3 pin
For the cooling FAN
Single phase AC200V±10% 50/60Hz 1.0Arms CN1-4, 5 pin
For control sources
DC24V±10% 0.5A CN2-1,2
An output power supply / 1 zone
Maximum Single phase AC200V±10% 50/60Hz TB1-1, 2 terminal
Application load
Resistance load (Fe-Cr-aluminum alloy)
AC200V / 50 KVA maximum /one zone or less
Control range
0-100% (0-200Vrms±10%)
Feedback control
Open-loop control system
Current limiting function
About 10 detection load current Aave(s) - 300Aave (setting variable)
Withstand voltage
AC2kV 1min between main circuit-drive housings
Insulation resistance
It is more than 10Mohm (DC 500V impression) between main circuit-drive housings.
Alarm output signal
Over-current detection alarm output
Short circuit detection alarm output
Disconnection detection alarm output
Element fault temperature alarm output
FAN rotation stop alarm output