Product line-up

HOT N2 heater and Temperature controller


 Hot N2 heater specification
Flow rate
200L/min or less
Output
Single phase AC200V 1kw
Temperature range
400℃ or less
Pressure range
0.5MPa or less
Dimension
φ90mm×395mm (a joint part except)
Connection joint
IN/OUT 3/8 Swagelok
Quality of an exothermic wire rod / form
KANTHAL APM / Wave type heating element
Material
SUS304
thermo couple for GAS TEMP control K type thermo couple One pair (3 m each of compensating leads)
The thermo couple for HEATAER TEMP over heat Please set up below one pair (3 m each of compensating leads) of K type thermo couple, and 600℃.

TAPE HEATER CONTROLLER Product specification
number of channels
1ch
Dimension
W:350mm×H:140mm×D:242mm
Temperature range
0〜50℃(without dew condensation)
Digital display
Two pieces (the object for GAS TEMP control, for HEATER TEMP over heat)
Control scheme
SSR control
Application load
Single phase AC200V 10A
Input power source
Single phase AC200V±10%
Thermo couple input
K type thermo couple
External input terminal
flow fall signal, an external input signal (dry contact input)
Input and output connectors
One with an output cable (3 m)
Power supply connection
M5 terminal box
External output connection
M4 terminal box.A point of contact.With an output cable (3 m)
Color
Mansel N3
Breaker
15A

Item
Connection place
Remarks
Power supply input terminal TB1-1, 2, 3 Single phase AC200V 1KVA Those with a ground
Heater output terminal TB2-1, 2 10A MAX
GAS TEMP thermo couple TB3-1, 2 K type thermo couple
HEATER TEMP thermo couple e TB3-3, 4 K type thermo couple
FL flow fall signal TB4-1, 2 Time of flow fall "Open" input (it sets to the preset temperature of 50℃)
External input signal TB4-3, 4 Time of abnormalities "Open" input (temp. cont. tone output stop)
Input and output connectors J1-1, 2 It is buzzer alarm at the time of the point of contact "Open"
J1-3, 4 It is a temp. cont. tone output stop at the time of the point of contact "Open"
J1-5, 6 GAS TEMP temp. cont. tone
Upper and lower limit alarm developmental time and point-of-contact "Open"
J1-7, 8 GAS TEMP temp. cont. tone
Overheat developmental time and point-of-contact "Open" Heater output stop
J1-9, 10 HEATER TEMP temp. cont. tone
Upper and lower limit alarm developmental time and point-of-contact "Open"
J1-10, 11 HEATER TEMP temp. cont. tone
Overheat developmental time and point-of-contact "Open" Heater output stop
J1-12, 13 HEATER TEMP temp. cont. tone
Overheat developmental time and point-of-contact "Open" Heater output stop

 

Safety specification
Over-current detection 2 The circuit protector 15A is installed in a temp. cont. heater line.
Upper and lower limit alarm
(GAS TEMP)
Preset value 240 It is an alarm output at the time the 100℃±50℃ range outside.
Upper and lower limit alarm
(HEATER TEMP)
Preset value 500 It is an alarm output at the time the 250℃±50℃ range outside.
Temperature anomaly alarm
(GAS TEMP)
Preset value 260 They are an alarm output and buzzer warning at the time of 120 or more ℃.
Temperature anomaly alarm
(HEATER TEMP)
Preset value 580 They are an alarm output, forced outage, and buzzer warning at the time of 250 or more ℃.
N2 flow detection It changes into a temp. cont. tone setup "50℃" at the time of a flow fall.