400 degrees celsius pure N2 suppling available
Free temperature setting with fale-safe function

HOT Hot N2 heater specification

Flow rate 200L/min or less
Output Single phase AC200V 1kw
Temperature range 400℃ or less
Pressure range 0.5MPa or less
Dimension φ90mm×395mm (a joint part except)
Connection joint IN/OUT 3/8 Swagelok
Quality of an exothermic wire rod / form KANTHAL APM / Wave type heating element
Material SUS304
thermo couple for GAS TEMP control K type thermo couple One pair (3 m each of compensating leads)
The thermo couple for HEATAER TEMP over heat Please set up below one pair (3 m each of compensating leads) of K type thermo couple, and 600℃.

TAPE HEATER CONTROLLER Product specification

number of channels 1ch
Dimension W:350mm×H:140mm×D:242mm
Temperature range 0〜50℃(without dew condensation)
Digital display Two pieces (the object for GAS TEMP control, for HEATER TEMP over heat)
Control scheme SSR control
Application load Single phase AC200V 10A
Input power source Single phase AC200V±10%
Thermo couple input K type thermo couple
External input terminal flow fall signal, an external input signal (dry contact input)
Input and output connectors One with an output cable (3 m)
Power supply connection M5 terminal box
External output connection M4 terminal box.A point of contact.With an output cable (3 m)
Color Mansel N3
Breaker 15A
Item Connection place Remarks
Power supply input terminal TB1-1, 2, 3 Single phase AC200V 1KVA Those with a ground
Heater output terminal TB2-1, 2 10A MAX
GAS TEMP thermo couple TB3-1, 2 K type thermo couple
HEATER TEMP thermo couple e TB3-3, 4 K type thermo couple
FL flow fall signal TB4-1, 2 Time of flow fall “Open” input (it sets to the preset temperature of 50℃)
External input signal TB4-3, 4 Time of abnormalities “Open” input (temp. cont. tone output stop)
Input and output connectors J1-1, 2 It is buzzer alarm at the time of the point of contact “Open”
J1-3, 4 It is a temp. cont. tone output stop at the time of the point of contact “Open”
J1-5, 6 GAS TEMP temp. cont. tone
Upper and lower limit alarm developmental time and point-of-contact “Open”
J1-7, 8 GAS TEMP temp. cont. tone
Overheat developmental time and point-of-contact “Open” Heater output stop
J1-9, 10 HEATER TEMP temp. cont. tone
Upper and lower limit alarm developmental time and point-of-contact “Open”
J1-10, 11 HEATER TEMP temp. cont. tone
Overheat developmental time and point-of-contact “Open” Heater output stop
J1-12, 13 HEATER TEMP temp. cont. tone
Overheat developmental time and point-of-contact “Open” Heater output stop

Safety specification

Over-current detection 2 The circuit protector 15A is installed in a temp. cont. heater line.
Upper and lower limit alarm
(GAS TEMP)
Preset value 240 It is an alarm output at the time the 100℃±50℃ range outside.
Upper and lower limit alarm
(HEATER TEMP)
Preset value 500 It is an alarm output at the time the 250℃±50℃ range outside.
Temperature anomaly alarm
(GAS TEMP)
Preset value 260 They are an alarm output and buzzer warning at the time of 120 or more ℃.
Temperature anomaly alarm
(HEATER TEMP)
Preset value 580 They are an alarm output, forced outage, and buzzer warning at the time of 250 or more ℃.
N2 flow detection It changes into a temp. cont. tone setup “50℃” at the time of a flow fall.